| 2007-07-12 15:08:52 | ****CORRECTIONS**** |
| | REVISED 8/26/7 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED |
| | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS FAC61G15-23 (APPLICATION FOR DEP).THESE |
| | SHEETS MAY BE VOIDED, BUT THE THE PLANS PREPARED BY |
| | JAMES BUSHOUSE, PE ARE TO INCLUDE ALL INFORMATION TO |
| | DETERMINE CODE COMPLIANCE. |
| | |
| | 2.)PROVIDE A SITE PLAN SHOWING WHERE THE DOCK WILL BE |
| | INSTALLED. |
| | |
| | 3.)GUARDS ARE REQUIRED EXCEPT AS EXEMPTED, FBC1012. |
| | PLANS ARE TO INDICATE EXEMPTION IF APPLICABLE.IF |
| | GUARDS ARE REQUIRED, PROVIDE A DETAIL AND SPECIFY |
| | DESIGN CRITERIA FBC1012, FBC1607.7. |
| | |
| | 4.)SHOW THE ACCESSIBLE ROUTE, FBC11-4. 1.2.SHOW |
| | SLOPE AND WIDTH.SPECIFY THE SPACING BETWEEN THE |
| | "TROPICAL DECKING" BOARDS. |
| | |
| | 5.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. |
| | |
| | NEW COMMENTS 8/28 |
| | |
| | 6.)DECLARE LEVEL OF ALTERATION ON THE PLAN, FBC EB |
| | CHAPTER 3. |
| | |
| | 7.)SCOPE OF WORK IS NOT CLEAR.APPLICATION STATES |
| | "REPLACE EXISTING DOCK", CONTRACTOR STATED ON THE |
| | TELEPHONE THAT APPROXIMATELY 35% IS BEING REPLACED. |
| | PLEASE MAKE SCOPE OF WORK, PLANS, AND APPLICATION |
| | DESCRIPTION CONSISTENT. |