Plan Review Notes
Plan Review Notes For Permit 07060304
Permit Number 07060304
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-04 09:15:49DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** THIS LOOKS LIKE ONE HALF OF THE 2 UNITS IS
 TURNING INTO A BUSINESS. THIS WOULD REQUIRE THE
 BATHROOM OR BATHROOMS TO BE HANDICAP ACCESSIBLE. SEE
 FBC-2004 EXISTING BUILDING, SECTION 506.1.
 NOTE: THIS COMMENT WAS NOT ADDRESSED ON THE
 RESUBMITTAL. IF THERE IS A CHANGE OF OCCUPANCY PLEASE
 INDICATE THIS ON THE RESUBMITTED PERMIT APPLICATION AS
 SUCH. PLEASE CLARIFY THIS ON THE RESUBMITTAL.
  
 2. **NO** SHOW ELEVATION DETAIL DRAWINGS WITH ALL THE
 REQUIRED MEASURMENTS/ INFORMATION TO COMPLY WITH
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILTY CODE SECTIONS
 11-4.23.1 THRU 11-4.23.9.
 NOTE: IF THERE IS A CHANGE OF OCCUPANCY ALL OF THE
 ABOVE INFORMATION IS REQUIRED. THIS COMMENT WAS NOT
 ADDRESSED ON THE RESUBMITTAL.
  
 3. **NO** ARE THE LAUNDRY FACILITIES BEING REMOVED?
 NOTE: IF SHEET 1 OF 6 IS SUPPOSED TO BE A DEMOLITION
 DRAWING PLEASE INDICATE THE REMOVAL OF THE LAUNDRY
 FACILITIES ON THE RESUBMITTAL.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 4. IF ONE HALF OF THIS UNIT IS TURNING INTO A BUSINESS
 A DRINKING FOUNTAIN IS REQUIRED PER FBC-2004, TABLE
 403.1, AND SHALL BE ADA ACCESSIBLE PER FBC-2004 CHAPTER
 11, SECTION 11-4.15.1 THRU 11-4.15.5 AND SECTION
 11-4.1.3(10) INDIVIDUALS WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved