| 2007-09-04 09:27:13 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07060304 |
| | ADD: 477 S.ROSEMARY AVE. |
| | CONT: OCEAN DRIVE BUILDING CORP. |
| | TEL: (561)833-3900 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)THE DRAWINGS PROVIDED DO NOT INDICATE CLEARLY THE |
| | SCOPE OF WORK.PROVIDE TWO COMPLETE SETS OF DRAWINGS |
| | WITH THE EXISTING FLOOR PLAN AND THE PROSOSED FLOOR |
| | PLAN.PAGE 1 OF 6 SHOWS TWO SEPERATE UNITS. PROVIDE |
| | SIMILAR DRAWINGS SHOWING HOW THE TWO UNITS WILL BECOME |
| | ONE. THE PLANS PROVIDED SHOWS ONLY ONE UNIT WITH A |
| | CASED OPENING. THE TOTAL FLOOR PLAN SHALL BE SHOWN. |
| | FBC. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL (SEE SECTION |
| | 106.3.5) |
| | |
| | NEW*** |
| | |
| | 1)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS |
| | A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | A)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & |
| | FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | |
| | B)UNITS 207 AND 209 APPEARS TO BE RESIDENTIAL UNITS. |
| | IF THESE UNITA ARE NOW BEING CHANGED AT BUSINESS, THE |
| | CHANGE OF OCCUPANCY OR USE BOX SHALL BE CHECKED ON THE |
| | APPLICATION. |
| | |
| | C) PROVIDE A LIFESAFETY PLAN SHOWING THE EGRESS PATH |
| | AND TRAVEL DISTANCE. FBC. (BUILDING) 1013. |
| | |
| | D) 1006.3.1. EXIT SIGNS:EXIT SIGNS SHALL BE MARKED BY |
| | AN APPROVED SIGN READILY VISIBLE FROM ANY DIRECTION OF |
| | EXIT ACCESS. EVERY EXIT SIGN SHALL BE SUITABLE |
| | ILLUMINATED BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND |
| | INTERNALLY ILLUMINATED SIGNS SHALL BE VISIBLE IN BOTH |
| | THE NORMAL & EMERGENCY LIGHTING. |
| | |
| | E)FBC. (BUILDING) 11-4.3.4 IF DOORWAYS HAVE TWO |
| | INDEPENDENTLY OPERATED DOORLEAVES, THEN ONE |
| | LEAF SHALL BE AT LEAST 32 INCHES. THE DOUBLE DOORS |
| | LEADING TO THE INTERIOR DESIGNER SPACE SHALL MEET THIS |
| | REQUIREMENT. |
| | |
| | F)SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE |
| | MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. 11-4.24.3 KNEE |
| | CLEARANCE THAT IS AT LEAST 27" HIGH 30" WIDE, AND 19" |
| | DEEP SHALL BE PROVIDED UNDERNEATH SINKS. 11-4.24.5 |
| | CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK. |
| | |
| | G) INDICATE THE INTERIOR WALL AND CEILING FINISH IN |
| | ACCORDANCE WITH FBC.TABLE 803.5. |
| | |
| | H)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | I)INDICATE CLEARLY THE TYPE OF BUSINESS AND THE USE |
| | OF EACH ROOM OR AREA ON THE PLANS. PROVIDE A WALL |
| | LEGEND AND SHOW WHERE EACH TYPE OF WALL WILL BE |
| | INSTALLED ON THE FLOOR PLANS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |