2007-06-20 10:15:03 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES SO THAT COMPLIANCE WITH CALCULATIONS FOR
 220.14(I) MAY BE REVIEWED.
  
 2} PROVIDE AMPERAGE RATINGS FOR EXISTING PANELS. BOTH
 PANELS ON SHEET 1/6 ARE DESIGNATED "D". REDESIGNATE FOR
 CIRCUIT CLARITY.
  
 3} SUBMIT A PANEL SCHEDULES PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 4} PROVIDE A CALCULATION FOR THE TRACK LIGHTING PER
 220.43(B).
  
 5} 2} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS.
  
 6} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  
 7} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  