| Plan Review Notes For Permit 07060304 |
| Permit Number |
07060304 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-20 10:15:03 | | | | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR | | | DEVICES SO THAT COMPLIANCE WITH CALCULATIONS FOR | | | 220.14(I) MAY BE REVIEWED. | | | | | | 2} PROVIDE AMPERAGE RATINGS FOR EXISTING PANELS. BOTH | | | PANELS ON SHEET 1/6 ARE DESIGNATED "D". REDESIGNATE FOR | | | CIRCUIT CLARITY. | | | | | | 3} SUBMIT A PANEL SCHEDULES PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. | | | | | | 4} PROVIDE A CALCULATION FOR THE TRACK LIGHTING PER | | | 220.43(B). | | | | | | 5} 2} PROVIDE EMERGENCY ILLUMINATION PER | | | NFPA-101 7.8 (2003), AND CIRCUITED PER | | | 700.12 NEC. INDICATE SAME ON PLANS. | | | | | | 6} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE | | | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE | | | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE | | | ARTICLE. | | | | | | 7} INDICATE COMPLIANCE WITH CHAPTER 13 | | | OF THE FLORIDA BLDG CODE. 13.413, | | | 13.414, 13.415. SHOW TIME CLOCK AND | | | OCCUPANCY SENSOR LOCATIONS ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|