| Plan Review Notes For Permit 07060293 |
| Permit Number |
07060293 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-19 12:01:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.)SEE ATTACHED SAMPLE INSTALLATION SCHEDULE.YOU | | | MAY USE AN ALTERNATE FORMAT BUT IT MUST INCLUDE ALL | | | INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE. | | | | | | 2.)YOU STATE THAT THIS IS A CBS HOUSE, BUT IS THE | | | SUBSTRATE FOR THE OPENINGS FILLED CELLS (WHICH WOULD BE | | | HOLLOW BLOCK ON THE PRODUCT APPROVAL), OR POURED | | | CONCRETE SUCH AS A TIE BEAM?SUBSTRATE INFORMATION | | | REQUIRED UNLESS YOU DESIGN TO THE MOST STRINGENT, WHICH | | | WOULD BE HOLLOW BLOCK. | | | | | | 3.)EDGE DISTANCE WAS NOT PROVIDED.HOWEVER, SEE | | | SHEET 5.THE 12" ANCHORING IS COMPLIANT FOR ONLY ONE | | | CONNECTION TYPE, C1, WITH A 3" EDGE DISTANCE. | | | | | | 4.)CONNECTION MOUNTING TYPE SHOULD BE C1 THROUGH C5, | | | SEE ANCHOR SCHEDULES ON THE PRODUCT APPROVAL. |
|