| Plan Review Notes For Permit 07060292 |
| Permit Number |
07060292 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-20 16:21:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS LINE 11A STATES AIR HANDLER | | | INTERIOR, MECHANICAL PLANS SHOW THE AIR HANDLER IS IN | | | THE GARAGE, PLEASE CORRECT ENERGY CALCULATIONS. | | | | | | 2) MECHANICAL PLANS NOTES STATE "ACCORDING TO | | | F.M.C.2004. AS THIS IS A SINGLE FAMILY DWELLING IT | | | NEEDS TO COMPLY WITH THE 2004 FBC/RESIDENTIAL, SEE | | | R101.2. PLEASE CORRECT. | | | | | | 3) MECHANICAL PLANS EQUIPMENT SCHEDULE, CAN NOT READ | | | THE CONDENSER UNIT MODEL NUMBER, SEE 2004 FBC 106.1.1. | | | PLEASE CORRECT. | | | | | | 4) PLEASE SHOW THE A/C SYSTEM'S SEER IN THE EQUIPMENT | | | SCHEDULE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. |
|