| 2007-08-17 16:59:11 | NEW SINGLE FAMILY RESIDENCE BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| | 2004 WITH 2006 REVISIONS. |
| | |
| | 1- TYPE OF CONSTRUCTION SPECIFIED ON SHEET 3.1 IS |
| | WRONG. SEE SEC. 602.1 FBC 2004 AND REVISE AS REQUIRED. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5115) TO PAY IMPACT FEES.BRING BACK STAMPED |
| | PLANS AND COPY OF PAID RECEIPT.REPEATED COMMENT FROM |
| | PREVIOUS CHECKLIST. |
| | |
| | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. REPEATED COMMENT FROM |
| | PREVIOUS CHECKLIST. |
| | |
| | 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. SEC. |
| | R401.3 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: WATER CAN'T BE DIRECTED TO NEIGHBOR'S |
| | PROPERTY. REPEATED COMMENT FROM PREVIOUS CHECKLIST. |
| | |
| | 5- SHEET 1.1: |
| | A) REVISE PLYWOOD ROOF SHEATHING NOTE D.MINIMUM |
| | FASTENER PENETRATIONIS 1 3/4" AS REQUIRED BY ASTM |
| | C-926 AND ASTM C-1063.THEREFORE 1 3/4" NAILING AS |
| | SPECIFIED ON THIS NOTE IS NOT ADEQUATE. SEE ASTM |
| | STANDARDS AND REVISE AS REQUIRED. |
| | |
| | B) UPDATE ALL GENERAL NOTES. SEE CHAPTER 43 OF 2004 |
| | FLORIDA RESIDENTIAL CODE FOR SPECIFIC STANDARDS AND |
| | SPECIFIC YEAR TO BE USED. REPEATED COMMENT FROM |
| | PREVIOUS CHECKLIST. |
| | |
| | 6- OWES $415.47 FOR UPDATED VALUATION AND RADON FEES. |
| | REPEATED COMMENT FROM PREVIOUS CHECKLIST. |
| | |
| | 7- PROVIDE SOIL TEST REPORT. REPEATED COMMENT-FROM |
| | PREVIOUS CHECKLIST. |
| | |
| | 8- ENERGY CALCULATIONS NEED TO HAVE CORRECT BUILDER'S |
| | NAME. REPEATED COMMENT FROM PREVIOUS CHECKLIST. |
| | |
| | 9- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) PRECAST LINTELS.NOA 03-0605.05 SUBMITTED |
| | EXPIRED ON 05/21/06. ON THE OTHER HAND NOA 03-0605.04 |
| | IS FOR 4", 6" AND 12" WIDE LINTELS. THEREFORE IT CAN BE |
| | USED IN THIS PROJECT BECAUSE THIS LINTEL SIZE IS NOT |
| | SPECIFIED ON PLANS. |
| | |
| | B) SINGLE HUNG WINDOWS. NOA 05-0928.03 SUBMITTED |
| | DON'T CORRESPOND TO FL239-R4 SUBMITTED. GO THE THE DCA |
| | WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD NOA THAT |
| | CORRESPONDS TO FL239. |
| | |
| | C) ENTRY DOOR AS SHOWN ON PLANS. REPEAT COMMENT FROM |
| | PREVIOUS CHECKLIST. |
| | |
| | D) FRENCH DOORS AS SHOWN ON PLANS.NOA 05-0107.01 |
| | SUBMITTED DOESN'T CORRESPOND TO FL253-R2 SUBMITTED. GO |
| | TO DCA WEBSITE TO DOWNLOAD CORRESPONDING NOA. |
| | ***NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS |
| | SUBMITTED. PROVIDE ONLY ONE PRODUCT APPROVAL. ON THE |
| | OTHER HAND NOA 02-1216.09 EXPIRED ON 08/15/07. |
| | THEREFORE IT CAN'T BE USED. |
| | |
| | 10- STORM SHUTTERS: |
| | A) COMPLETE ALL THE INFORMATION IN THE INSTALLATION |
| | SCHEDULE SUBMITTED. NEED TO SPECIFY SHUTTER MOUNTING |
| | CONDITION (EG: WALL MOUNTED, BUILT OUT MOUNTED, ETC.), |
| | SHUTTER SPAN, SPECIFIC ANCHOR AND SUBSTRATE (STRUCTURE |
| | TO BE ATTACHED TO: CONCRETE BLOCK). |
| | |
| | B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC ANCHOR |
| | TYPE. SEE SHEET 5 OF 6 OFSHUTTERS DRAWINGS. |
| | |
| | C) PROVIDE KEY PLAN TO IDENTIFY LOCATION OF |
| | OPENINGS. |
| | |
| | 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- SHEET 2.1: REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT |
| | WAY OF SHOWING BUCK DETAIL.BUCK NEEDS TO PROVIDE |
| | FULL FRAME SUPPORT. REPEAT COMMENT FROM PREVIOUS |
| | CHECKLIST. |
| | |
| | 13- SHEET 5.1:ROOF DESIGN LOADS INFORMATION DOESN'T |
| | MATCH INFORMATION SHOWN ON SHEET. 1.1.REVISE AS |
| | REQUIRED. REPEATED COMMENT FROM PREVIOUS CHECKLIST. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |