| 2007-07-11 17:59:31 | BUILDING REVIEW CHECKLIST: |
| | 1- PLANS TO SPECIFY CONSTRUCTION TYPE AS REQUIRED BY |
| | SEC. 602.1 OF FBC 2004. |
| | |
| | 2- GARAGE DOOR LEADING TO THE LIVING ROOM AREA NEEDS TO |
| | COMPLY WITH SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. PROVIDE SPECS FOR DOOR THAT COMPLIES WITH THIS |
| | CODE SECTION. |
| | |
| | 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5115)TO PAY IMPACT |
| | FEES. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT. |
| | |
| | 4- BRING RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 5- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE:WATER CAN'T BE DIRECTED TO THE NEIGHBOR'S |
| | PROPERTY. |
| | |
| | 6- REVISE ROOF SHEATHING NOTES ON SHEET 1.1,ROOF |
| | FRAMING PLANS AND PLYWOOD SHEATHING NAILING SCHEDULE. |
| | MINIMUM TYPE OF NAIL IS 8D RING SHANK NAIL AND SPACING |
| | AT ZONE 3IS 4" ON CENTER. SEESEC. R803.2.3.1 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 7-VALUATION DECLARED ON PERMIT APPLICATION WAS |
| | UPDATED AS REQUIRED BY SEC. 108.3 CITY AMENDMENTSTO |
| | FBC 2004.THEREFORE OWES $415.47 FOR VALUATION UPDATE |
| | AND RADON FEES. |
| | |
| | 8- PROVIDE SOIL TEST REPORT.2 COPIES WITH ORIGINAL |
| | ENGINEER'S SEAL AND SIGNATURE. |
| | |
| | 9- ENERGY CALCULATIONS: |
| | A) PROVIDECORRECT BUILDER INFORMATION. AND, |
| | COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | B) CLARIFY ITEM 9 (B): WHERE IS THE EXTERIOR |
| | CONCRETE WALL WITH R11 INSULATION? ANDHOW IS THE R11 |
| | VALUE ACHIEVED. |
| | |
| | 10- ENERGY CALCULATIONS ARE TAKEN THE CEILING FANS |
| | CREDIT. THEREFORE, PLANS NEED TO SHOW SIZE OF CEILING |
| | FAN IN ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1FBC |
| | 2004. |
| | |
| | 11- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED |
| | BY DCA RULE 9B-72 FOR: |
| | A) ENTRY DOOR. |
| | B) FRENCH DOORS AS SHOWN ON PLANS. |
| | C) SINGLE HUNG WINDOWS. |
| | D) STORM SHUTTERS IF SINGLE HUNG WINDOWS DON'T HAVE |
| | IMPACT GLASS. |
| | ***NOTE: NEED TO PROVIDE STORM SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.AND, MARK |
| | ON SHUTTERS DRAWINGS SPECIFIC SHUTTER MOUNTING |
| | CONDITIONS (EG: WALL MOUNTED)AND SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED ACCORDING TO DESIGN PRESSURES, |
| | EDGE DISTANCE, CONNECTION TYPE, PANEL SPAN AND |
| | STRUCTURE TO BE ATTACHED TO (CONCRETE BLOCK).SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | E) 8" PRECAST LINTELS AS SPECIFIED ON PLANS. CLARIFY |
| | WHY ENGINEER APPROVED PRODUCT APPROVAL FOR 4", 6" AND |
| | 12" PRECAST LINTELS IF THEY WERE NOT USED? |
| | |
| | 12- SHEET 1.1: |
| | A) REVISE DESIGN CRITERIAITEM (D). WHAT ARE THE |
| | WIND ZONES AVERAGE PRESSURES? WHERE ARE THESE TAKEN |
| | FROM?. IS THIS REALLY REQUIRED? ALL ZONES ARE MIXED UP? |
| | THESE WIND ZONES ARE FOR WHAT?. WALLS, ROOF?. WHAT'S |
| | THE CONSIDERED TRIBUTARY AREA ?.ARE THESE FOR |
| | COMPONENTS AND CLADDING? SEE 2006 REVISED TABLE |
| | 1609.6.2.1(2). |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) REVIEW ALL NOTES AND UPDATE THE SPECIFIC STANDARD |
| | AND YEAR TO BE REFERENCED IN THE CODE. SEE CHAPTER 43 |
| | OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT REFERENCE |
| | STANDARD AND YEAR TO BE USED FOR EACH CHAPTER OF THE |
| | CODE. |
| | |
| | C) MASONRY WALL NOTES:SEE SEC. R606.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE AND REVISEMINIMUM NET AREA |
| | COMPRESSIVE STRENGTH OF CONCRETE BLOCK. |
| | |
| | 13- SHEET 2.1: REVISE WINDOW BUCK DETAIL.SEE SEC. |
| | R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER |
| | WAY OF INSTALLING THE BUCK. |
| | WINDOW/DOORFRAME NED TO HAVE FULL SUPPORT ON THE |
| | BUCK. |
| | |
| | 14- SHEET 5.1:ROOF DESIGN LOADS INFORMATION DOESN'T |
| | MATCH INFORMATION GIVEN ON SHEET 1.1. REVISE AS |
| | REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |