Plan Review Notes
Plan Review Notes For Permit 07060281
Permit Number 07060281
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-25 10:35:31 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PANEL DESIGNATIONS AND CIRCUIT NUMBERS GIVEN FOR
 THE EQUIPMENT ARE INCORRECT PER PERMITTED SET OF PLANS.
 THE GEAR SHOWN FEEDING THE COMPRESSERS ARE NOT ON THIS
 BUILDING. SEE 230.3
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  