| Plan Review Notes For Permit 07060281 |
| Permit Number |
07060281 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-02 08:38:48 | DENIED | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | **FOR PLAN REVIEW ONLY NOT FOR PERMIT AT THIS TIME** | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. NOTE: A COMPLETE ISOMETRIC RISER DIAGRAM WITH PIPE | | | SIZES, VALVE LOCATIONS, QUICK-DISCONNETS, AND INCLUDING | | | TJE UNDERGROUND PIPING AND CONNECTIONS. | | | | | | 2. NOTE: PLEASE SUBMIT TWO COPIES OF MANUFACTURER | | | SPECIFICATIONS/CUT SHEETS THAT SHOW A LISTING FROM A | | | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) FOR THE | | | FOLLOWING. PLEASE PROVIDE MANUFACTURER SHEETS THAT | | | EQUIPMENT IS DESIGNED FOR OUTDOOR USE. | | | A} INFINITY PIPE (90000 CALIBRATED ALUMINUM | | | PIPING) AND FITTINGS (D20, D25, D32, D40MM). | | | B} AIR COMPRESSORS. | | | C} DRYER. | | | D} TANK A & B. | | | 3. NOTE: PROVIDE A DETAIL INDICATING HOW THE EQUIPMENT | | | IS TO BE ANCHORED FOR WIND LOADS PER THE FOLLOWING. | | | FBC-2004 | | | A} SECTION, 1603.1.4 WIND DESIGN DATA. | | | B} SECTION, 1609.1.3 ANCHORAGE AGAINST | | | OVERTURNING, UPLIFT AND SLIDING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS REVIEWER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|