| Plan Review Notes For Permit 07060281 |
| Permit Number |
07060281 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-13 16:01:45 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PANEL DESIGNATIONS AND CIRCUIT NUMBERS GIVEN FOR | | | THE EQUIPMENT ARE INCORRECT PER PERMITTED SET OF | | | PLANS. | | | | | | 2} SPECIFY COPPER OR ALUMINUM CONDUCTORSON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|