2007-07-11 16:19:30(PLAN REVIEW ONLY) DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE. THE
 EQUIPMENT PAD IS REQUIRED TO BE AT 7.5' ABOVE BFE.
  
 3) SUBMIT DETAILS FOR THE CONCRETE EQUIPMENT PAD AND
 SPECIFY HOW THE EQUIPMENT WILL BE ATTACHED TO RESIST
 WINDLOADS. SEE FBC 106.1.2* AND 1609.1.3.
  
 4) SPECIFY THE APPLICABLE WIND DESIGN DATA ON THE
 PLANS. SEE FBC 1603.1.4.
  