| Plan Review Notes For Permit 07060276 |
| Permit Number |
07060276 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-26 21:02:49 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY | | | POWER SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 110. | | | | | | 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | | GENERATOR. | | | | | | 4.PROVIDE DISTANCE OF AT LEAST 10' TO BUILDING | | | OPENINGS ARE ACHIEVED. | | | | | | 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE GENERATOR | | | AND ASSOCIATED EQUIPMENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|