2007-07-26 21:02:49*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 110.
  
 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4.PROVIDE DISTANCE OF AT LEAST 10' TO BUILDING
 OPENINGS ARE ACHIEVED.
  
 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE GENERATOR
 AND ASSOCIATED EQUIPMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  