| 2007-06-23 18:32:39 | *** UNSAT *** |
| | |
| | ** AS THERE IS SUBSTANTIAL INFORMATION NOT SUBMITTED, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW AS |
| | MANY ITEMS CAN NOT BE REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS DONE BY AN ENGINEER PER FS |
| | 471.003(2)(H)(2A) |
| | THE SCOPE OF WORK DOES NOT MEET THE EXCEPTIONS FOR AN |
| | ELECTRICAL CONTRACTOR. |
| | PLEASE SEE COMMENTS FROM BUILDING FOR POSSIBLE REQUIRED |
| | ENGINEER SLAB/TIE DOWN INFORMATION. |
| | |
| | 2) NOTE:PLEASE SUBMIT COMPLETED SITE PLANS, SURVEY |
| | ETC. PLEASE SEE ZONING AND COMMENTS FROM OTHER TRADES |
| | FOR PLANS NEEDED. THE SIZE OF THE TANK WILL HAVE |
| | COMMENTS FROM MECHANICAL REVIEWER. |
| | PLEASE SEE BUILDING COMMENTS AS NO PLANS WERE SUBMITTED |
| | FOR SLAB, CONNECTIONS, ETC. |
| | PLEASE INDICATE ALL DIMENSIONS ON PLANS, SITE PLANS, |
| | AND SURVEY. |
| | PLEASE PROVIDE INFORMATION IF IN A FLOOD ZONE AND KNOW |
| | THE ELEVATION WILL BE NEEDED ON PLANS. |
| | FBC 106.1, 106.3.5.1.2 |
| | THERE ARE SEVERAL ITEMS NOT KNOWN AT THIS TIME AND CAN |
| | NOT BE REVIEWED. |
| | |
| | 3) NOTE: PLEASE KNOW THE FOLLOWING CODES WILL BE |
| | REQUIRED ON PLANS FOR DESIGN AND SCOPE OF WORK. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2002 NFPA-110 |
| | 2005 NFPA-70 |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR |
| | OTHER CODES WHICH MAY BE REQUIRED. |
| | |
| | 4) NOTE: PLEASE SUBMIT TWO COMPLETE PACKAGES OF |
| | MANUFACTURE SPECS/CUT SHEETS FOR ALL EQUIPMENT |
| | INCLUDING THE FOLLOWING. |
| | GENERATOR, GENERATOR ENCLOSURE, FUEL TANK(S) ETC. |
| | SOME OF THESE ITEMS WILL BE REVIEW BY OTHER TRADE(S). |
| | NEC 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| | GENERATOR, ATS, MAIN(S), DESIGN COSTS ETC EVEN IF ANY |
| | OF THIS IS OWNER SUPPLIED. |
| | THE VALUE AS SHOWN IS EXTREMELY LOW AND A VALUE MAY BE |
| | ASSESSED BY THIS OFFICE BASED ON GUIDES ADOPTED BY THE |
| | FLORIDA BUILDING CODE. |
| | THE COST SHALL INCLUDE ALL. |
| | FBC 108.3 |
| | |
| | 6) NOTE: PLEASE SUBMIT PLANS WITH A COMPLETE LAYOUT OF |
| | ALL EXISTING ELECTRICAL SERVICE EQUIPMENT AT THIS |
| | BUILDING. PLEASE INDICATE ALL MAINS, DISCONNECTS ETC. |
| | AT THIS TIME AS THE LOCATION OF THESE ITEMS ARE NOT |
| | CLEAR, NO REVIEW OF LOCATIONS CAN BE DONE. |
| | PLEASE KNOW THAT NO DISCONNECTING MEANS IS SHOWN AND |
| | ONE WILL BE REQUIRED. PLEASE KNOW THE BREAKER IN THE |
| | GENERATOR MAY NOT BE USED DUE TO REQUIREMENTS FROM |
| | ZONING AND DOES NOT MEET THE EXCEPTIONS IN THE NEC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 230.70,230.71,230.72, 225.31-225.39, 702.11 PLEASE |
| | SEE MISSING DISCONNECTING MEANS AS REQUIRED. THIS IS |
| | BASED ON NO INFORMATION PROVIDED. |
| | |
| | 6) NOTE: PLEASE PROVIDE THE OCP ON THE GENERATOR. |
| | FBC 106.1.2, NEC 240.4, 310.16, 445.13 ETC. |
| | |
| | 7) NOTE: PLEASE PROVIDE COMPLETED ROUTE OF CONDUITS FOR |
| | REVIEW. PLEASE KNOW IF ANY RATED WALLS ARE PENETRATED, |
| | MUST PROVIDE THE UL LISTING, ANSI, ASTM STANDARDS ETC. |
| | THESE WALL DETAILS WILL BE REVIEWED AND RATINGS ON |
| | WALLS WILL BE NEEDED. THERE ARE RATED WALLS BASED ON |
| | THE BRIEF INFORMATION PROVIDED AND THIS INFORMATION IS |
| | NEEDED. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 300.21 |
| | |
| | ** ALL COMMENTS ABOVE SHOULD BE FORWARDED TO THE |
| | ENGINEER WHO WILL BE TAKING OVER PROJECT AND MAY NEED |
| | THIS INFORMATION FROM REVIEWER(S). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |