Plan Review Notes
Plan Review Notes For Permit 07060276
Permit Number 07060276
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-17 16:21:19BUILDING PLAN REVIEW
 PERMIT: 07060276
 ADD: 1700 PALM BEACH LAKES BLVD
 CONT: ALL-PRO ELECTRICAL
 TEL: (561)239-3097
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
  
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED INDICATE THEY WERE PRODUCED BY KAMM
 CONSULTING ENGINEERING, THEY APPEAR TO BE COPIES,
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 4) THE VALUE OF THE PERMIT IS LOW, THE TOTAL JOB COST
 ARE TO INCLUDE THEOWNER BAUGHTGENERATOR. IF THE
 VALUE IS NOT DECLARED THE CITY WILL USE MARSHALL &
 SWIFT TO ESTAMATE THE VALUES AND THE PERMIT FEES WILL
 BE ADJUSTED ACCORDINGLY. 108.3 FLB ADMINISTRATIVE
 CODE.
  
 5) PLEASE PROVIDE A SITE PLAN WITH THE LOCATION OF THE
 GENERATOR AND ALL BUILDINGS PROVIDE DIMENSIONS OF
 CLOSENESS TO BUILDINGS AND ALSO INDICATE WINDOWS AND
 DOORS IN THE WALLS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 6) PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR
 VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE
 VENTS, ETC.
  
 MECHANICAL CODE 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE MOUNTED
 DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY
 FROM AN OIL TANK VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED
 GRADE.
  
 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219
 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1
 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO PREVENT RAIN
 FROM ENTERING THE VENT SYSTEM.
 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICALEXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN ATTIC OR
 CRAWL SPACE
  
 401.5 OPENING LOCATION. OUTDOOR AIR EXHAUST AND INTAKE
 OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET (3048
 MM) FROM LOT LINES OR BUILDINGS ON THE SAME LOT. WHERE
 OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO
 THE CENTERLINE OF THE STREET OR PUBLIC WAY.
  
 7) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]