| 2007-07-17 16:21:19 | BUILDING PLAN REVIEW |
| | PERMIT: 07060276 |
| | ADD: 1700 PALM BEACH LAKES BLVD |
| | CONT: ALL-PRO ELECTRICAL |
| | TEL: (561)239-3097 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED INDICATE THEY WERE PRODUCED BY KAMM |
| | CONSULTING ENGINEERING, THEY APPEAR TO BE COPIES, |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | |
| | 4) THE VALUE OF THE PERMIT IS LOW, THE TOTAL JOB COST |
| | ARE TO INCLUDE THEOWNER BAUGHTGENERATOR. IF THE |
| | VALUE IS NOT DECLARED THE CITY WILL USE MARSHALL & |
| | SWIFT TO ESTAMATE THE VALUES AND THE PERMIT FEES WILL |
| | BE ADJUSTED ACCORDINGLY. 108.3 FLB ADMINISTRATIVE |
| | CODE. |
| | |
| | 5) PLEASE PROVIDE A SITE PLAN WITH THE LOCATION OF THE |
| | GENERATOR AND ALL BUILDINGS PROVIDE DIMENSIONS OF |
| | CLOSENESS TO BUILDINGS AND ALSO INDICATE WINDOWS AND |
| | DOORS IN THE WALLS. |
| | 106.1.2* ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6) PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR |
| | VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE |
| | VENTS, ETC. |
| | |
| | MECHANICAL CODE 804.3.4 HORIZONTAL TERMINATIONS. |
| | HORIZONTAL TERMINATIONS SHALL COMPLY WITH THE FOLLOWING |
| | REQUIREMENTS: |
| | 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE |
| | TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT |
| | LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE |
| | WALKWAY. |
| | 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) |
| | ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 |
| | MM). |
| | 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET |
| | (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR |
| | 1 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR |
| | INLET INTO THE BUILDING. |
| | 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED |
| | CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER |
| | FORMED BY TWO WALLS PERPENDICULAR TO EACH OTHER. |
| | 5.THE VENT TERMINATION SHALL NOT BE MOUNTED |
| | DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY |
| | FROM AN OIL TANK VENT OR GAS METER. |
| | 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE |
| | LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED |
| | GRADE. |
| | |
| | 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS |
| | SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: |
| | 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE |
| | TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT |
| | LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE |
| | WALKWAY. |
| | 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) |
| | ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 |
| | MM). |
| | 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN |
| | ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE |
| | LOCATED AT LEAST 3 FEET (914 MM) FROM SUCH STRUCTURE. |
| | 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219 |
| | MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1 |
| | FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR |
| | INLET FOR THE BUILDING. |
| | 5.A VENT CAP SHALL BE INSTALLED TO PREVENT RAIN |
| | FROM ENTERING THE VENT SYSTEM. |
| | 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3 |
| | FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF |
| | STRUCTURE. |
| | |
| | 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY |
| | MECHANICALEXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS |
| | AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM |
| | WHICH IT |
| | CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING |
| | SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN ATTIC OR |
| | CRAWL SPACE |
| | |
| | 401.5 OPENING LOCATION. OUTDOOR AIR EXHAUST AND INTAKE |
| | OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET (3048 |
| | MM) FROM LOT LINES OR BUILDINGS ON THE SAME LOT. WHERE |
| | OPENINGS FRONT ON A |
| | STREET OR PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO |
| | THE CENTERLINE OF THE STREET OR PUBLIC WAY. |
| | |
| | 7) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE |
| | SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOAD REDUCTION.SECOND, PROVIDE |
| | INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH, |
| | IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |