| Plan Review Notes For Permit 07060235 |
| Permit Number |
07060235 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-06 14:08:45 | ***DENIED*** | | | | | | PLEASE NOTE THAT THERE IS NO RESPONSE TO THE FIRST FIRE | | | REVIEW. PLEASE SEE REVIEW COMMENTS TAKEN FROM PREVIOUS | | | FIRE REVIEW: | | | | | | 1) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2) THE REMOVAL OF AND/OR THE STOCKING OF NEW BUILDING | | | MATERIALS AND SUPPLIES SHALL NOT HINDER, INTERFERE OR | | | OBSTRUCT ACCESS TO OR EGRESS FROM THE PROPERTY | | | INCLUDING THE FLOOR'S EXIT CORRIDORS. | | | | | | 3) PLEASE INDICATE IF THE ERECTION OF THE NEW PARTITION | | | WALL IMPACTS FIRE SPRINKLER DEVICES. SEPARATE SHOP | | | DRAWINGS AND PERMIT IS REQUIRED IF THE FIRE PROTECTION | | | SYSTEM HAS TO BE MODIFIED. | | | PLEASE RESPOND ON PLANS OR RESPONSE LETTER | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|