2007-12-03 12:11:32 
  
 PERMIT #07060228
 ELECTRICAL PLAN REVIEW
 826 HIGH STREET
 12/3/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THESE ITEMS THAT WERE REDLINED ON THE PERMIT SET OF
 PLANS WERE NOT INCLUDED ON THE REVISION. INCLUDE SAME
 FOR COMPLIANCE WITH THE FOLLOWING ARTICLES.
  
 A) 210.63 HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.
  
 B) 210.8(A) DWELLING UNITS ALL 125-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED
 IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 210.8(A)(6) KITCHENS ? WHERE THE RECEPTACLES ARE
 INSTALLED TO SERVE THE COUNTERTOP SURFACES.
  
 C) 210.52 DWELLING UNIT RECEPTACLE OUTLETS. (E)
 OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING AND EACH UNIT
 OF A TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT
 LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT GRADE LEVEL
 AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  
 THIS IS A COMMENT GENERATED BY THE REVISION SUBMITTED.
  
 2} THE NOTE ON THE PLAN INDICATES A WALL BEING REMOVED,
 BUT THE WALL REMAINS INCLUDED IN THE REVISION, AND
 DEVICES ARE LOCATED ON SAME. RESUBMIT REVISION TO
 CLEARLY INDICATE THE SCOPE OF THE WORK TO BE DONE.
 106.1.3 FBC AS AMENDED.
  
 3} IT IS UNCLEAR WHAT THE SYMBOLS AT THE SINK REFER TO,
 PLEASE CLARIFY. 106.1.3 FBC.
  
 4} THIS IS A REVISION, NOT A SUBMITTAL, FEES ARE DUE,
 PAY SAME WHEN PLANS ARE PICKED UP.
  
 NOTE: A BUILDING REVISION IS REQUIRED FOR REMOVING THE
 WALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]