2007-06-18 12:11:30 
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE FOUR SETS OF PLANS SUBMITTED THAT DO NOT
 MATCH. SUBMIT TWO COPIES OF PLANS, THAT ARE ALIKE, FOR
 REVIEW. THE PLANS MUST BE DRAWN WITH ENOUGH CLARITY TO
 DETERMINE SPACING REQUIREMENTS ARE CORRECT PER CODE.
 BATHS AND KITCHEN MUST INCLUDE CABINET LAYOUT.
  
 2} HAND DRAWN PLANS IN PENCIL ARE NOT ACCEPTABLE FOR
 RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3 FBC
 AS AMENDED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 4] THE PLANS INCLUDED A RISER DIAGRAM, BUT A NOTE
 INDICATES THAT THE SERVICE IS EXISTING. PLEASE REMOVE
 ALL PLANS THAT ARE NOT TO BE IN THE SCOPE OF THIS
 APPLICATION.
  
 5} INCLUDE THE CONDUCTOR SIZES ON THE PANEL SCHEDULE SO
 COMPLIANCE WITH 310.16 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  