| Plan Review Notes For Permit 07060228 |
| Permit Number |
07060228 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-18 12:11:30 | | | | | | | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} THERE ARE FOUR SETS OF PLANS SUBMITTED THAT DO NOT | | | MATCH. SUBMIT TWO COPIES OF PLANS, THAT ARE ALIKE, FOR | | | REVIEW. THE PLANS MUST BE DRAWN WITH ENOUGH CLARITY TO | | | DETERMINE SPACING REQUIREMENTS ARE CORRECT PER CODE. | | | BATHS AND KITCHEN MUST INCLUDE CABINET LAYOUT. | | | | | | 2} HAND DRAWN PLANS IN PENCIL ARE NOT ACCEPTABLE FOR | | | RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3 FBC | | | AS AMENDED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | 4] THE PLANS INCLUDED A RISER DIAGRAM, BUT A NOTE | | | INDICATES THAT THE SERVICE IS EXISTING. PLEASE REMOVE | | | ALL PLANS THAT ARE NOT TO BE IN THE SCOPE OF THIS | | | APPLICATION. | | | | | | 5} INCLUDE THE CONDUCTOR SIZES ON THE PANEL SCHEDULE SO | | | COMPLIANCE WITH 310.16 CAN BE REVIEWED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|