| Plan Review Notes For Permit 07060216 |
| Permit Number |
07060216 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-11-26 08:21:16 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | SAME COMMENTS AS PREVIOUS TWO REVIEWS: | | | | | | 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK | | | INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO | | | REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT | | | PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC | | | AS AMENDED. | | | | | | 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH | | | 210.52(A)(1 & 2), IN THE SUNROOM.* CLARIFY IF THIS IS A | | | SUNROOM OR SCREEN ENCLOSURE. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.3.4.3.FBC.. * THIS INCLUDE THE ELECTRICAL SHEETS. | | | THE PLANS MUST BE DRAWN WITH CLARIT PER 106.1.3 FBC AS | | | AMENDED. | | | | | | RESPOND TO ALL COMMENTS IN WRITING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|