2007-06-08 16:54:26BUILDING REVIEW CHECKLIST:
 1- NOA #04-0506.03 SUBMITTED FOR FLAT ROOF ASSEMBLY
 EXPIRED ON 05/23/07. NEED TO PROVIDE CURRENT NOA.
  
 2-SELECTED ASSEMBLY ON PAGE 16 OF NOA SUBMITTED SHOWS
 2 DIFFERENT BASE SHEET FASTENING OPTIONS. PLEASE MARK
 WHICH OPTION IS GOING TO BE USED.
  
 3- SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION
 #7.PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 AND TABLE 1609.6.2.1(2) OF FBC 2004.
  
 ***NOTE:
 SEE ATTACHED CITY POLICY FOR ROOFING PERMITS AND
 INFORMATION REQUIRED FOR PLAN REVIEW.
  