| Plan Review Notes For Permit 07060213 |
| Permit Number |
07060213 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-08 16:54:26 | BUILDING REVIEW CHECKLIST: | | | 1- NOA #04-0506.03 SUBMITTED FOR FLAT ROOF ASSEMBLY | | | EXPIRED ON 05/23/07. NEED TO PROVIDE CURRENT NOA. | | | | | | 2-SELECTED ASSEMBLY ON PAGE 16 OF NOA SUBMITTED SHOWS | | | 2 DIFFERENT BASE SHEET FASTENING OPTIONS. PLEASE MARK | | | WHICH OPTION IS GOING TO BE USED. | | | | | | 3- SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION | | | #7.PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 AND TABLE 1609.6.2.1(2) OF FBC 2004. | | | | | | ***NOTE: | | | SEE ATTACHED CITY POLICY FOR ROOFING PERMITS AND | | | INFORMATION REQUIRED FOR PLAN REVIEW. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|