2007-06-07 14:57:49PLANS ROUTED TO LUIS MARTINEZ
2007-06-07 14:26:52 
 ** UNSAT **
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL WIRING DIAGRAM FOR
 ALL NEW ELECTRICAL PUMP EQUIPMENT, CONDUCTOR SIZES,
 OVER CURRENT PROTECTION, CIRCUIT, PANEL SCHEDULE AND
 LOAD CALCULATIONS.
 310.16,240.4,408.4,220,ETC
 PLEASE SEE 680.50-56
 FBC 106.1.2, 106.3.5
  
 2) NOTE: PLEASE SUBMIT DETAIL FOR UNDER WATER LIGHTING,
 TRANSFORMER, DECK BOX?
 GROUNDING, BONDING ETC AS REQUIRED. 250.50, 680.50-56
 AS NOTED ABOVE IN NOTE #1.
  
 3) NOTE: PLEASE BE SURE THE MOST RECENT ADOPTED CODES
 RELEVANT TO SCOPE OF WORK AND DESIGN IS STATED ON
 PLANS.
 FBC 2004 W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
  
 ** PLANS INDICATE THE 2002 FBC , 2002 NEC AND THE
 *SOUTH FLORIDA BUILDING CODE* WHICH HAS NOT BEEN IN
 EFFECT IN THE STATE OF FLORIDA SINCE THE 2001 FBC WAS
 ADOPTED.
  
 ** REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 PER FAC 61G15-23.002 AND FS 471.023
 MISSING THE FIRM CERTIFICATE OF AUTHORIZATION NUMBER.
  
 ** REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy