Plan Review Notes
Plan Review Notes For Permit 07060198
Permit Number 07060198
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-26 19:41:11BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 1)FBC 1609.1WIND PRESSURES.BASED ON THE RWDI WIND
 TUNNEL TEST REPORT, SHEET S-6.00 OF THE STRUCTURAL
 PLANS FOR THE BUILDING (UNDER PERMIT # 05091425) SHOWS
 NEGATIVE WINDPRESSURES RANGING FROM -70 PSF TO -150
 PSF.THESE DESIGN PRESSURE ARE FAR HIGHER THAN THE
 PRESSURES ASSUMED IN THE SUBMITTED ATLANTIC & CARIBBEAN
 ROOFING CONSULTING, LLC REPORTS 06-1274 L REV. AND
 06-1274 H REV. (BOTH DATED 6/5/07) FOR THE
 DESIGN/SELECTION OF THE TILE AND ATTACHMENT FOR THE
 LOWER AND HIGHER ROOF.SUBMIT CALCULATIONS THAT MEET
 THE DESIGN PRESSURES ON STRUCTURAL PLAN SHEET S-6.00.
 IT IS NOTED THAT THE ATLANTIC & CARIBBEAN ROOFING
 CONSULTING, LLC REPORTS 06-1274 L AND 06-1274 H (BOTH
 DATED 8/15/06, PRIOR TO REVISION) DID MEET THE REQUIRED
 WIND PRESSURES, AND WERE CONSEQUENTLY REVIEWED AND
 STAMPED ON 9/9/06 UNDER PERMIT # 05091425.
  
 2) FBC* 106.3.3ALL PRODUCT APPROVALS AND CALCULATIONS
 SHALL BE REVIEWED BY THE DESIGNER OF RECORD AND STAMPED
 WITH HIS/HER SHOP DRAWING REVIEW STAMP PRIOR TO
 SUBMITTAL FOR BUILDING OFFICIAL REVIEW. THERE ARE NO
 SHOP DRAWING REVIEW STAMPS FROM THE DESIGNER OF RECORD
 ON ANY OF THE SUBMITTED DOCUMENTS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS