| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, WITH |
| | ORIGINAL COMMENT NUMBER ATTACHED. |
| | |
| | 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS |
| | SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR |
| | FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE |
| | SEE ARTICLE. |
| | A)COMMENT TO RESPONSE. THIS ARTICLE DOES APPLY.AS |
| | THERE ARE NO EXEPTIONS LISTED IN THAT ARTICLE. SEE |
| | DETAIL #1, SHEET E7.1, DETAILS 02, 03, 04 AND 05, SHEET |
| | A-2.. A NOTE ON THE PLAN REFERENCING THIS ARTICLE WILL |
| | SUFFICE |
| | |
| | 5} PROVIDE EMERGENCY ILLUMINATION PER |
| | NFPA-101 7.8 (2003), AND CIRCUITED PER |
| | 700.12 NEC. INDICATE SAME ON PLANS. |
| | A) THIS IS REQUIRED IN THE PLAN REVIEW STAGE OF THE |
| | PERMITTING PROCESS, THE CIRCUITING MUST BE REVIEWED FOR |
| | COMPLIANCE. |
| | |
| | 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND |
| | ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE |
| | REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A |
| | CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED. |
| | A) SAME COMMENT AS ABOVE.. |
| | |
| | 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS. |
| | INDICATE CIRCUIT NUMBERS. |
| | |
| | SEE 553.80(2)(B), ATTACHED, REGARDING DESIGN |
| | PROFESSIONALS DOCUMENTS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |