| 2007-06-22 12:28:18 | *****DENIED***** |
| | |
| | |
| | 01.ON SHEET A-T1 UNDER APPLICABLE CODES, AMEND TO |
| | REFLECT THAT NFPA 1 (2003 EDITION) AND NFPA 101 (2003 |
| | EDITION) SHALL BE REFERENCED. |
| | |
| | 02.PLEASE EXPLAIN THE REFERENCES TO NFPA 45, NFPA |
| | 88B-97, AND NFPA 102-95 UNDER THE APPLICABLE CODES. ARE |
| | THESE REFERENCES PERTINENT TO THE PROPOSED SCOPE OF |
| | WORK? |
| | |
| | 03.THE TENANT SPACE SUITE NUMBER SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE PREMISES AT THE END OF EACH |
| | SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE |
| | OPERATION. |
| | |
| | 06.THE REMOVAL OF EXISTING AND/OR THE STOCKING OF NEW |
| | BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE OR |
| | HINDER ACCESS TO OR EGRESS FROM THE SAID TENANT SPACE |
| | OR OTHER TENANT SPACES ON THE 17TH FLOOR. |
| | |
| | 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH |
| | MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE |
| | SPECIFIC |
| | |
| | 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS. |
| | |
| | 09.PLANS DO NOT STATE OR SHOW THE PRESENCE OF THE |
| | TENANT SPACE BEING SPRINKLERED.IF SPRINKLERED AND |
| | MODICATIONS TO THE SYSTEM IS NEEDED, SEPARATE PLANS AND |
| | PERMIT SHALL BE REQUIRED. |
| | |
| | 10.PLANS DO NOTSTATE OR SHOW THE PRESENCE OF FIRE |
| | ALARM OR FIRE ALARM DEVICES FOR THIS TENANT SPACE.IF |
| | SO EQUIPPED AND MODICATIONS TO THE SYSTEM IS NEEDED, |
| | SEPARATE PLANS AND PERMIT WILL BE REQUIRED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |