| 2007-06-20 08:02:50 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| | CHANGE. |
| | |
| | 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS |
| | SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR |
| | FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE |
| | SEE ARTICLE. |
| | |
| | 3} THE "SIMPLEX LOCK" NOTED ON SHEET A-E1, MUST BE |
| | PERMITEDUNDER SEPARATE APPLICATION, WITH ALL |
| | EQUIPMENT SPECIFICATION. |
| | |
| | 4} SHEET NOTES ON ELECTRICAL SHEETS INDICATE A SHEET |
| | E7.2, THIS SHEET IS MISSING. |
| | |
| | 5} PROVIDE EMERGENCY ILLUMINATION PER |
| | NFPA-101 7.8 (2003), AND CIRCUITED PER |
| | 700.12 NEC. INDICATE SAME ON PLANS. |
| | |
| | 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND |
| | ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE |
| | REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A |
| | CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED. |
| | |
| | 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS. |
| | INDICATE CIRCUIT NUMBERS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |