Plan Review Notes
Plan Review Notes For Permit 07060197
Permit Number 07060197
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-18 16:53:50 
 PROJECT: 777 SOUTH FLAGLER, WEST TOWER, SUITE #1701
 PLAN REVIEW: 2004 FLORIDABUILDING AND EXISTING
 BUILDING CODE WITH 2006 REVISIONS
 1ST REVIEW
 STATUS: DENIED
  
  
 PLAN REVIEW COMMENTS:
  
 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE
 MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS
 NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE.
 FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE
 PERMIT ISSUANCE.
  
 2) 105.8 NOTICE OF COMMENCEMENT.
  
 AS PER SECTION 713.135, FLORIDA STATUTES, WHEN ANY
 PERSON APPLIES FOR A BUILDING PERMIT, THE AUTHORITY
 ISSUING SUCH PERMIT SHALL PRINT ON THE FACE OF EACH
 PERMIT CARD IN NO LESS THAN 18-POINT, CAPITALIZED,
 BOLDFACED TYPE:"WARNING TO OWNER: YOUR FAILURE TO
 RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
 PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU
 INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR
 AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF
 COMMENCEMENT."
  
 3)301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING
 DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) OCCUPANCY LOAD
 C) OCCUPANCY GROUP
 D) SPRINKLERED OR NON-SPRINKLERED.
  
 5) INDICATE EXIT SIGNS AS PER FBC 1006.3 ON SHEETS
 A-LS1 AND A-2, SAFETY AND REFLECTED CEILING PLAN
 RESPECTIVELY:
  
 1006.3 EXIT SIGNS.
  
 1006.3.1
 EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT
 SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY
 LIGHTING.
 EXCEPTION: MAIN EXTERIOR EXIT DOORS THAT OBVIOUSLY AND
 CLEARLY ARE IDENTIFIABLE AS EXITS.
  
 6) PLEASE INDICATE TRAVEL DISTANCESAND THE OCCUPANCY
 LOAD ON THE LIFE SAFETY PLAN AS PER THE WEST PALM BEACH
 ADMINISTRATIVE CODE, SECTION 106.3.5.1.1(7).
  
 6A)605.4.1TWO EGRESS DOORWAYS REQUIRED.
  
 WORK AREAS SHALL BE PROVIDED WITH TWO EGRESS DOORWAYS
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS
 605.4.1.1 AND 605.4.1.2.
 605.4.1.1
 OCCUPANT LOAD AND TRAVEL DISTANCE.
 IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN
 OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL
 DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL
 HAVE A MINIMUM OF TWO EGRESS DOORWAYS.
 EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES
 HAVING A MAXIMUM OCCUPANT LOAD OF 10.
  
  
 7) PLEASE PROVIDE PRODUCT SPECIFICATIONS FOR THE
 FOLLOWING:
  
  
 A) NEW CARPET AS INDICATED ON SHEET A-ID1.
 B) WALL COVERING AS INDICATED BY MARK WC-2 ON SHEET
 A-ID1.
 C) NEW ENGINEERED WOOD FLOORING, MARK WF-1 ON SHEET
 A-ID1.
  
 PLEASE NOTE THAT ALL NEWLY INSTALLED INTERIOR
 FINISHES SHALL COMPLY WITH THE FLORIDA BUILDING CODE,
 SECTION 803.5:
  
 803.5 INTERIOR FINISH REQUIREMENTS BASED ON
 GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME
 SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE
 803.5 FOR THE GROUP AND LOCATION DESIGNATED. INTERIOR
 WALL AND CEILING FINISH MATERIALS, OTHER THAN TEXTILES,
 TESTED IN ACCORDANCE WITH NFPA 286 AND MEETING THE
 ACCEPTANCE CRITERIA OF SECTION 803.2.1, SHALL BE
 PERMITTED TO BE USED WHERE A CLASS A CLASSIFICATION IN
 ACCORDANCE WITH ASTM E 84 IS REQUIRED.
  
 8) PLEASE PROVIDE EXISTING/NEW DOOR SCHEDULE.
  
 9) PLEASE INDICATE THE EXISTING RATED WALL PARTITIONS
 AND FIRE RESISTIVITY ON THE OVERALL FLOOR PLAN, SHEET
 A-1.
  
 10) RAISED FLOORING SHALL CONFORM TO THE FOLLOWING
 REQUIREMENTS OF FBC 717.2.7
  
 717.2.7 CONCEALED SLEEPER SPACES.
  
 WHERE WOOD SLEEPERS ARE USED FOR LAYING WOOD FLOORING
 ON MASONRY OR CONCRETE FIRE-RESISTANCE-RATED FLOORS,
 THE SPACE BETWEEN THE FLOOR SLAB AND THE UNDERSIDE OF
 THE WOOD FLOORING SHALL BE FILLED WITH AN APPROVED
 MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND
 PRODUCTS OF COMBUSTION OR FIREBLOCKED IN SUCH A MANNER
 THAT THERE WILL BE NO OPEN SPACES UNDER THE FLOORING
 THAT WILL EXCEED 100 SQUARE FEET (9.3 M2) IN AREA AND
 SUCH SPACE SHALL BE FILLED SOLIDLY UNDER PERMANENT
 PARTITIONS SO THAT THERE IS NO COMMUNICATION UNDER THE
 FLOORING BETWEEN ADJOINING ROOMS.
 EXCEPTIONS:
  
 1.FIREBLOCKING IS NOT REQUIRED FOR SLAB-ON-GRADE FLOORS
 IN GYMNASIUMS.
 2.FIREBLOCKING IS REQUIRED ONLY AT THE JUNCTURE OF EACH
 ALTERNATE LANE AND AT THE ENDS OF EACH LANE IN A
 BOWLING FACILITY.
  
 11) ALL WOOD BUCKS AND BLOCKING TO BE FIRE RETARDANT
 TREATED LUMBER AS PER THE FOLLOWING:
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I
 OR II CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE
 PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE.
 COMBUSTIBLE PIPING SHALL BEPERMITTED WITHIN
 CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, PLUMBING.
  
  
 12) PROVIDE DETAILS FOR THE INSTALLATION OF THE NEW
 CLORESTORY WINDOWS:
  
 A) GLAZING SPECIFICATIONS.
 B) WALL FRAMING/ATTACHMENT DETAILS.
  
 13) PROVIDE NEW METAL WALL AND CEILING FRAMING DETAILS
 AS REFLECTED ON SHEET A-3 DETAIL 06 AND SECTION 05/A6.
  
 14) PLEASE PROVIDEAN OVERALL DEMOLITION FLOOR PLAN,
 SHEET A-D1 FOR CONSTRUCTION CLARIFICATION AS PER THE
 FOLLOWING:
  
 106.1 SUBMITTAL DOCUMENTS.
 CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA SHALL
 BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION
 FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A DESIGN PROFESSIONAL WHERE REQUIRED BY THE
 STATUTES. WHERE SPECIAL CONDITIONS EXIST, THE BUILDING
 OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL
 CONSTRUCTION DOCUMENTS TO BE PREPARED BY A DESIGN
 PROFESSIONAL.
  
  
 BUILDING PLANS EXAMINER: KEN CONRAD
 PHONE: 561.805.6666
 FAX: 561.805.6676