Plan Review Notes
Plan Review Notes For Permit 07060192
Permit Number 07060192
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-11 08:46:02******************PROVISO*******************
  
 THE MANUAL ACTUATION DEVICE (REMOTE PULL STATION) SHALL
 BE LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE
 COOKING AREA, A MINIMUM OF 10 FEET AND A MAXIMUM OF 20
 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE MANUAL
 ACTUATION DEVICE SHALL BE LOCATED A MINIMUM OF 4 FEET
 AND A MAXIMUM OF 5 FEET ABOVE THE FLOOR. THE MANUAL
 ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40 POUNDS
 AND A MAXIMUM MOVEMENT OF 14 INCHES (356 MM) TO ACTUATE
 THE FIRE SUPPRESSION SYSTEM. FBC 904.11.1
  