| Plan Review Notes For Permit 07060191 |
| Permit Number |
07060191 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-13 11:00:00 | *** PROVISO *** | | | 1) PROVIDE FOR RETURN AIR TO BEDROOMS, SEE 2004 FBC/R | | | M1602.4. | | | | | | 2) THE DWELLING WILL BE REQUIRED TO HAVE SMOKE ALARMS | | | INSTALLED IF NOT ALREADY PRESENT, PER 2004 FBC/R | | | 313.1.1, AND SEE 2004 FEBC 303.1 LEVEL ONE ALTERATION | | | INCLUDE REPLACEMENT OF EQUIPMENT. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|