| Notes |
| Date |
Text |
| 2007-07-05 17:28:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)SEE PREVIOUS LIST REGARDING SPECIFYING CONNECTION | | | MOUNTING TYPE.THIS WAS NOT REVISED.HOWEVER, WALL | | | MOUNT 2 AND WALL MOUNT 4 HAVE ITEMS CIRCLED.WALL | | | MOUNT 2 IS FOR POURED CONCRETE ONLY, YOU STATE THAT | | | THIS JOB HAS A CBS SUBSTRATE.PLEASE ADDRESS. | | | | | | 2.)POSITIVE DESIGN PRESSURES FOR THE SHUTTERS ARE NOT | | | CLEAR FROM THE PRODUCT APPROVALS SUBMITTED.IF YOU | | | WISH TO DESIGN TO +205, THIS IS ACCEPTABLE BUT PROVIDE | | | SOMETHING FROM THE MANUFACTURER OR ENGINEER WHICH SHOWS | | | COMPLIANCE WITH YOUR DESIGN CRITERIA.IT IS STILL NOT | | | CLEAR AS TO WHY YOU ARE SPECIFYING A POSITIVE PRESSURE | | | OF 205, BUT A NEGATIVE PRESSURE OF 120. | | | | | | |
|