| Plan Review Notes For Permit 07060185 |
| Permit Number |
07060185 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-19 10:25:06 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)TWO COMPLETE SETS REQUIRED. | | | | | | 2.)THE PRODUCT APPROVALS ARE DIFFICULT TO READ AND | | | SHEET 1 HAS BEEN CUT.PLEASE PRINT CLEAN, LEGIBLE, | | | INTACT PRODUCT APPROVALS.THEY MAY BE AVAILABLE FROM | | | WWW.FLORIDABUILDING.ORG. | | | | | | 3.)IT IS NOT CLEAR WHICH MOUNTING TYPE YOU ARE USING; | | | RATHER THAN STATING "WALL" OR "FLOOR", PLEASE PROVIDE | | | THE DESIGNATION ON THE ANCHOR SHEDULES ON SHEETS 10 | | | THROUGH 12. | | | | | | 4.)YOU ARE DESIGNING TO +205, ACCORDING TO YOUR | | | INSTALLATION SCHEDULE.IT IS ACCEPTABLE TO EXCEED CODE | | | COMPLIANCE.PLEASE CONTACT ME BY TELEPHONE IF YOU NEED | | | ASSISTANCE WITH DETERMINING DESIGN PRESSURES. | | | |
|