| Notes |
| Date |
Text |
| 2007-09-21 07:03:40 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | CITY MUNICIPAL CODE | | | | | | 1. NEW P-1 SHEET SHOWS THE COOLING TOWER DRAIN AND | | | OVERFLOW DRAINING TO THE SAME SANITARY RISER STACK. THE | | | DRAIN SHALL DRAIN TO THE SANITARY, BUT THE OVERFLOW | | | SHALL DRAIN TO STORM. IT CAN BE PIPED TO THE NEAREST | | | ROOF DRAIN. ARTICLE III SECTION 90-125(5). PLEASE | | | CORRECT THE PLUMBING SHEET TO REFLECT THESE | | | REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|