| Plan Review Notes For Permit 07060182 |
| Permit Number |
07060182 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-02 17:38:52 | ---------------DENIED------------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | NFPA 214-96 | | | | | | 1. SCHEMATIC AND INLET DETAILS SECTION IS NOT LEGIBLE. | | | PLEASE PROVIDE MARLEY SCHEMATIC THAT IS OF LEGIBLE | | | SIZE, QUALITY AND CLARITY. FBC 106.1.3 | | | | | | 2. DETAILS FOR PIPE STANDS AND CLAMPS: SUFFICIENT | | | INFORMATION IS NOT PROVIDED WITH DETAILS AS SHOWN ON | | | PLAN. PROVIDE ALL RELEVANT INFORMATION ON PLANS, SUCH | | | AS SIZE, FASTENERS TO BE USED, SPACING OF SUPPORTS, | | | ETC. RATHER THAN REFERRING TO A CATALOG WHICH WAS NOT | | | PROVIDED WITH THE APPLICATION. FBC 106.1.1, 106.1.3 | | | | | | 3. PROVIDE MANUFACTURER'S SUBMITTAL DATA AND | | | INSTALLATION INSTRUCTIONS FOR THE COOOLING TOWER. FBC,M | | | 908.1 | | | | | | 4. PROVIDE WIND LOAD CALCULATIONS FOR THE COOLING | | | TOWER, SUPPORTS AND ANCHORING SHOWING THE DESIGN TO BE | | | ADEQUATE FOR THE WIND ZONE AND EXPOSURE CATEGORY OF THE | | | JOB LOCATION PER FBC,M 301.13 AND FBC CH.16. | | | | | | 5. PLEASE REFERENCE CODES IN EFFECT AT TIME OF PERMIT | | | APPLICATION: FBC 2004 W/2006 REVISIONS, NFPA 214-96. | | | | | | NOTE: ADDITIONAL COMMENTS ARE POSSIBLE PENDING THE | | | INCLUSION OF INFORMATION WHICH IS MISSING AT THIS | | | TIME. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|