| 2007-06-21 20:01:16 | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE |
| | THE CODES TO BE STATED ON PLANS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE PROVIDE INFORMATION FOR ANY INCREASE OF |
| | LOADS FROM EXISTING EQUIPMENT TO NEW EQUIPMENT. THIS |
| | INFORMATION SHOULD BE STATED ON PLANS. |
| | 220. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE RISER MENTIONS FOR GUTTER TO BE |
| | REPLACE PER NEC HOWEVER NO SIZE OR DIMENSIONS ARE SHOWN |
| | AS NEEDED PER NEC 366. |
| | FBC 106.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |