| Plan Review Notes For Permit 07060181 |
| Permit Number |
07060181 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-08 16:10:32 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | FOURTH REVIEW BUT FIRST REVIEW FOR INSTALLATION | | | SCHEDULE | | | | | | 1.)SHUTTER MOUNTING CONNECTION TYPE (INSTALLATION | | | SCHEDULE) SHOULD BE THE CONNECTION TYPE, C1 THROUGH C5, | | | SEE SHEET 5 OF THE PRODUCT APPROVAL. | | | | | | 2.)INSTALLATION SCHEDULE STATES THAT YOU WILL BE | | | INSTALLING TAPCONS.THERE ARE TWO TYPES, ELCO AND ITW, | | | AND YOU HAVE HIGHLIGHTED ELCO BUT HIGHLIGHTED ANCHORING | | | FOR ITW, WHICH REQUIRES 6" ANCHOR SPACING, BUT YOU | | | SPECIFY 12".COMPLETE INFORMATION REQUIRED ON THE | | | INSTALL SCHEDULE (SEE NOTE ON THE BOTTOM OF THE | | | INSTALLATION SCHEDULE WHICH STATES "ANCHOR TYPE MUST BE | | | SPECIFIC, EG THERE ARE DIFFERENT TYPES OF TAPCONS WITH | | | DIFFERENT STRENGTH VALUES"THERE IS INCOMPLETE | | | INFORMATION ON THE SCHEDULE AND INCONSISTENT | | | INFORMATION ON THE PRODUCT APPROVAL. |
|