| 2008-08-12 12:53:53 | |
| | ** DENIED PLANS.** |
| | |
| | ** NEW PLANS ONCE AGAIN WHICH ARE COMPLETELY REVISED |
| | FROM PREVIOUS PLANS. |
| | ** NEW DESIGNER OF RECORD. |
| | |
| | 1) NOTE: THE GENERATOR IS NOW BEING SHOWN AS A |
| | SEPARATELY DERIVED SYSTEM HOWEVER THE RISER INDICATES A |
| | 3-POLE TRANSFER SWITCH. |
| | PLEASE EXPLAIN HOW THIS IS POSSIBLE. |
| | 250.20, 250.30, ETC. |
| | |
| | 2) NOTE: AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | 250.110,250.24,250.122 ETC. |
| | THE RISER FOR FEEDERS FROM ATS TO EXISTING MAIN AT |
| | BUILDING IS MISSING AN EQUIPMENT GROUNDING CONDUCTOR. |
| | 250.32, 250.122. |
| | MUST ALSO PLACE NOTE ON PLANS TO SEPARATE ALL NEUTRALS |
| | AND EQUIPMENT GROUNDING AT EXISTING MAIN ONE OF ONE. |
| | |
| | |
| | ** MUST INSTALL EQUIPMENT GROUNDING. THE ONLY WAY |
| | EQUIPMENT GROUNDING IS NOT REQUIRED IS *IF* THERE ARE |
| | NO OTHER METAL CURRENT CARRYING PARTS BETWEEN SOURCES |
| | OR EQUIPMENT. BASED ON THE BRANCH CIRCUIT FROM THE |
| | EXISTING SERVICE TO GENERATOR AND OTHER POSSIBLE |
| | CURRENT CARRYING PARTS THIS IS REQUIRED. |
| | |
| | 3) NOTE: BASED ON COMMENT #1 ABOVE PLEASE SUBMIT |
| | REVISED SPECS/CUT SHEETS FOR TRANSFER SWITCH. 110.3, |
| | 90.7 |
| | |
| | 4) NOTE: THIS RISER IS NOW SHOWING MAINS AND |
| | DISCONNECTING MEANS WHICH WERE NEVER PREVIOUSLY SHOWN. |
| | ALL MAINS AND MEANS OF DISCONNECT SHALL MEET CODE FOR |
| | GROUPING AND ALSO FOR SIGNAGE REQUIRED AND LABELING ALL |
| | MEANS OF DISCONNECT FOR SHUTTING DOWN POWER UNDER BOTH |
| | CONDITIONS. |
| | 230.2E, 700.8, 701.9, 702.8 |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |