| 2008-05-30 08:09:57 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SEVERAL NEW COMMENTS ARE NOW BASED ON |
| | COMPLETELY REVISED ELECTRICAL RISER DIAGRAM WHICH NOW |
| | CONTAINS SEVERAL NEW CHANGES WHICH WERE NOT PART OF |
| | PREVIOUSLY SUBMITTED PLANS. |
| | |
| | 1) NOTE: PLEASE SEE PLANS NOW SHOW A NEW 500KVA |
| | TRANSFORMER WHICH WAS NOT PART OF PREVIOUS PLANS. |
| | PLEASE SEE 250.20,250.30 AS THIS IS NOW A SEPARATELY |
| | DERIVED SYSTEM. |
| | |
| | 2) NOTE: PLEASE SEE THE TRANSFORMER AS NOTED ABOVE IS |
| | ALSO SHOWING NEUTRAL CONDUCTORS TO THE TRANSFORMER. HOW |
| | IS THIS POSSIBLE WHEN THE TRANSFORMER IS SEPARATELY |
| | DERIVED? |
| | PLEASE COMPLETE PLANS, CONDUCTORS, RISER, GROUNDING |
| | ELECTRODE SYSTEM ETC PER 2005 NEC. |
| | THERE ARE TOO MANY CODE SECTIONS TO NOTE. |
| | FBC 106.3.5.1.2 |
| | NEC 225, 230, 240, 250, ETC. |
| | |
| | 3) NOTE: PLEASE SEE RISER WHICH SHOWS TWO BLACK LINES |
| | FROM THE GENERATOR. ONE IS SHOWN TO TRANSFER SWITCH AND |
| | THE OTHER TO THE TRANSFORMER. WHAT IS THIS SECOND |
| | LINE? |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE RISER IS STILL SHOWING EQUIPMENT |
| | GROUNDING CONDUCTORS BEFORE THE FIRST MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. |
| | 250.6, 250.24 |
| | |
| | ** THERE ARE SEVERAL ITEMS WHICH CAN NOT BE DETERMINED |
| | AT THIS TIME. HOWEVER PLEASE SEE THE COMMENTS ABOVE AND |
| | PLEASE TAKE A LOOK AT THE PLANS/RISER SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |