| 2008-03-08 17:51:53 | ** DENIED 2NDREVIEW** |
| | |
| | ** PLEASE SEE SOME OF THE EXACT SAME COMMENTS FROM |
| | PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING ALONG |
| | WITH SOME NEW COMMENTS BASED ON NEW PLANS SUBMITTED FOR |
| | REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS NOW SUBMITTED ARE |
| | PHOTO-COPIES OF SIGNED, DATED AND SEALED PLANS. PLEASE |
| | SEE FAC 61G15-23.002 AND FS 471.025 WHICH REQUIRES ALL |
| | DOCUMENTS TO CONTAIN ORIGINAL SIGNATURES, DATES AND |
| | RAISED SEALS. THIS IS REQUIRED WHETHER OR NOT COMMENT |
| | IS MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE STILL NO LOAD |
| | CALCULATIONS SUBMITTED AS PREVIOUSLY REQUESTED. PLEASE |
| | SEE NFPA-70 2005 220.87 AND SUBMIT. THE LOADS IN AMPS |
| | SHOWN ON RISER CAN NOT BE VERIFIED, WHAT IS THE |
| | VOLTAGE? |
| | 702.5 |
| | |
| | 3) NOTE: PLEASE KNOW A LICENSED CONTRACTOR OTHER THAN |
| | THE ELECTRICAL CONTRACTOR AS SIGNED ON WILL BE REQUIRED |
| | FOR STRUCTURAL WORK. EC MAY NOT PERFORM WORK AS SHOWN. |
| | PLEASE ALSO SEE THE VALUE FOR COMPLETE SCOPE OF WORK |
| | INCLUDING STRUCTURAL HAS NOT BEEN ADJUSTED. |
| | PLEASE SEE FBC 108.3. |
| | |
| | 4) NOTE: PLEASE SEE RISER AS THIS STILL SHOWS AN |
| | *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS |
| | OF DISCONNECT WHICH IS NOT PERMITTED. AS THE CODE |
| | REQUIRES BONDING AT THE FIRST MEANS OF DISCONNECT ANY |
| | EQUIPMENT GROUNDING CONDUCTORS INSTALLED BEFORE THE |
| | FIRST MEANS OF DISCONNECT WOULD PARALLEL THE NEUTRAL |
| | AND CREATE OBJECTIONABLE CURRENTS. |
| | PLEASE SEE THE RISER WHICH SHOWS THIS SAME 1/0 AS |
| | EXISTING WHICH IS NOT POSSIBLE. AS THE INSIDE MSB IS |
| | NOW AFTER THE FIRST MEANS OF DISCONNECT ONLY NOW WOULD |
| | THE EQUIPMENT GROUNDING CONDUCTOR BE INSTALLED AND |
| | NEEDS TO BE SHOWN AS NEW. |
| | PLEASE ALSO PLACE NOTE ON PLANS AS ALL NEUTRALS AND |
| | EQUIPMENT GROUNDS WILL BE REQUIRED TO BE SEPARATED IN |
| | EIXSITNG EQUIPMENT. |
| | 250.24, 250.6 |
| | |
| | 5) NOTE: PLEASE SEE THE RISER DOES NOT SHOW ANY BREAKER |
| | AT THE GENERATOR AND THE SPECS SUBMITTED DOES NOT |
| | CLEARLY SHOW A BREAKER OR OVER CURRENT PROTECTION? |
| | PLEASE KNOW AS NOTED ABOVE FOR LOAD CALCULATIONS, AS |
| | THE VOLTAGE FOR SYSTEM COULD NOT LOCATED, WE CAN NOT |
| | DETERMINE SOME ITEMS FOR CODE COMPLIANCE AT THIS TIME. |
| | 240.4, 310.16, 445.13. |
| | |
| | 6) NOTE: PLEASE SEE THE GENERATOR SPECS INDICATE |
| | CHARGING FOR BATTERY ETC HOWEVER THE PLANS DO NOT SHOW |
| | ANY ELECTRICAL FROM SERVICE TO THESE ITEMS. |
| | BLOCK HEATER? BATTERY CHARGER? ETC |
| | 408.4, 240.4, 310.16, ETC |
| | PLEASE PROVIDE ADDITIONAL INFORMATION. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |