| Date |
Text |
| 2007-06-23 17:59:57 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE SUBMITTED PLANS MAY NOT BE |
| | DONE BY AN ELECTRICAL CONTRACTOR. THIS SCOPE OF WORK |
| | INCLUDING ELECTRICAL, SLAB WORK ETC SHALL BE DONE BY A |
| | PROFESSIONAL ENGINEER AS REQUIRED UNDER FS 471.003 THE |
| | DOCUMENTS SUBMITTED DOE NOT CORRELATE FOR ELECTRICAL. |
| | NO REVIEW WAS DONE AS ENGINEERED PLANS ARE NEEDED AND |
| | THE SHEETS SUBMITTED DO NOT CORRELATE. PLEASE SEE |
| | BUILDING REVIEW COMMENTS AS ENGINEERING WILL ALSO BE |
| | REQUIRED FOR SLAB AND ATTACHMENT. THE 6INCH SLAB AS |
| | SHOWN DOES NOT PROVIDE THE INFORMATION NEEDED. PLEASE |
| | PROVIDE COMPLETED PLANS FOR ALL ELECTRICAL AND OTHER |
| | WORK FOR REVIEW. |
| | FBC 106.1, 106.3.5.1.2, 106.1.2 |
| | |
| | 2) NOTE: PLEASE KNOW THE FOLLOWING CODES WILL BE |
| | REQUIRED ON PLANS FOR DESIGN AND SCOPE OF WORK. 2004 |
| | FBC W/2006 REVISIONS. |
| | 2002 NFPA-110 |
| | 2005 NFPA-70 |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR |
| | OTHER CODES WHICH MAY BE REQUIRED. |
| | |
| | 3) NOTE: PLEASE SUBMIT TWO COMPLETE PACKAGES OF |
| | MANUFACTURE SPECS/CUT SHEETS FOR ALL EQUIPMENT |
| | INCLUDING THE FOLLOWING. |
| | THESE PACKAGES SHOULD BE BOUND TOGETHER IN SOME FASHION |
| | WITH TABS OF SOME SORT TO LABEL EACH IN PACKAGE. |
| | GENERATOR, MAIN SWITCHGEAR, ATS, GENERATOR ENCLOSURE, |
| | FUEL TANK(S) ETC. |
| | NEC 110.3, 90.7. |
| | FBC 106.1.2 |
| | * SOME OF THESE WERE SUBMITTED, HOWEVER NOT ALL WHICH |
| | IS NEEDED. |
| | |
| | 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR , MATERIALS, EQUIPMENT, |
| | GENERATOR, ATS, MAIN(S), DESIGN COSTS ETC EVEN IF ANY |
| | OF THIS IS OWNER SUPPLIED. |
| | FBC 108.3 |
| | |
| | 5) NOTE: PLEASE SEE 250.6, 250.24 AS NO * EQUIPMENT |
| | GROUNDING CONDUCTOR * IS INSTALLED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. |
| | |
| | 6) NOTE: PLEASE BE SURE COMPLETE LOAD CALCULATIONS ARE |
| | SUBMITTED FOR EXISTING SERVICE. |
| | PLEASE CLARIFY HOW THE 2000AMP SERVICE IS NOW BEING |
| | DOWN-SIZED TO 1400AMPS?? |
| | |
| | ** ALL COMMENTS ABOVE SHOULD BE FORWARDED TO THE |
| | ENGINEER WHO WILL BE TAKING OVER PROJECT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |