Plan Review Notes
Plan Review Notes For Permit 07060154
Permit Number 07060154
Review Stop B
Sequence Number 3
Notes
Date Text
2007-09-18 08:37:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)DESIGNER OF RECORD FOR THE BUILDING, JEFFREY
 GASPAR, IS TO REVIEW THE DRAWINGS (SHOP DRAWING REVIEW
 STAMP).
  
 3RD REQUEST; NOT ADDRESSED.
  
 2.)SEE FBC TABLE 302.3.2.THE FIRE SEPARATION IS TO
 BE IN COMPLIANCE WITH FBC TABLE 302.3.2 EXCEPT FOR
 NONSEPARATED USE, FBC302.3.1.IF THIS CAN BE A
 NONSEPARATED USE, PLEASE SHOW CALCULAATIONS ON THE PLAN
 FBC302.3.1, FBC TABLE 503.
  
 SEE COMMENT 3.A NONSEPARATED USE WAS DECLARED BUT THE
 PLANS DO NOT SHOW COMPLIANCE WITH FBC TABLE 503.
  
 3.)SHOW HOW THE NEW OCCUPANCY COMPLIES WITH FBC TABLE
 503.
  
 3RD REVIEW - THE PLANS STATE THAT THIS IS A TYPE III B
 BUILDING, AND THAT THE FLORIDA BUILDING CODE 2004
 COMMENTARY STATES THAT A FBC 2001 TYPE V B IS NOW A
 TYPE III B.PLEASE NOTE THE FOLLOWING -
  
 A.PLEASE ADVISE AS TO WHERE THIS LANGUAGE IN THE
 COMMENTARY IS LOCATED AS I AM UNABLE TO FIND IT.ALSO
 PLEASE NOTE THE INCONSISTENCY; THE 2001 CODE CLASSIFIED
 BUILDINGS AS "PROTECTED" AND "UNPROTECTED", NOT "A" OR
 "B".
  
 B.THE COMMENTARY AND THE CODE BOTH STATE THAT A 2HOUR
 FIRE RESISTANCE RATING IS REQUIRED FOR TYPE III B; SEE
 PAGE 6-2 OF THE COMMENTARY AND FBC602.3,FBC TABLE
 601.ALSO SEE ATTACHED COMMENTARY WHICH I HAVE
 HIGHLIGHTED.
  
 C.PLANS STATE THAT THE EXTERIOR WALL IS 1 HOUR;
 THEREFORE, CANNOT BE A TYPE III B.IF THE PLANS ARE
 INCORRECT AND THE EXTERIOR BEARING WALLS ARE 2 HOUR,
 PLEASE REVISE PLAN AND PROVIDE A DETAIL SHOWING HOW THE
 EXISTING WALLS COMPLY WITH THE 2HOUR REQUIREMENT AS I
 BELIEVE THE BUILDING WAS PERMITTED WITH NO FIRE
 RESISTANCE REQUIRED FOR EXTERIOR WALLS.
  
 D.PLEASE SEE FBC 506.2 REGARDING FRONTAGE INCREASES;
 COULD THIS SECTION APPLY?CALCULATIONS WERE PROVIDED
 WHICH SHOW ALLOWABLE OPENINGS BUT DO NOT STATE DISTANCE
 TO PROPERTY LINE.BASED ON FBC TABLE 704.8, 45%
 INDICATES THAT EACH EXTERIOR WALL IS 20-25' FROM THE
 PROPERTY LINE; THEREFORE, IT APPEARS THAT A FRONTAGE
 INCREASE MAY POSSIBLY RESOLVE THE ISSUE.
  
 5.)REGARDING IMPACT FEES, PLEASE BE ADVISED THAT PALM
 BEACH COUNTY HAS DETERMINED THAT IMPACT FEES ARE NOT
 REQUIRED AT THIS TIME.HOWEVER, FUTURE TENANT
 BUILDOUTS MAY REQUIRE AN IMPACT FEE ASSESSMENT (PER
 WILLIE SWOPE AND GWEN, PALM BEACH COUNTY, 233-5025).
  