Plan Review Notes
Plan Review Notes For Permit 07060154
Permit Number 07060154
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-13 19:12:042007-07-13 19:12:04
 **** UNSAT ****
  
 1) NOTE: PLEASE SEE THE PREVIOUS NOTE #1 AS THIS
 REQUESTED FOR THE CERTIFICATION SHEETS OF THE ENERGY
 CALCULATIONS TO BE SIGNED ETC AS REQUIRED PER
 13-103.1.1.1 OF THE FBC.
 PLEASE SEE THE OWNER AGENT IS STILL NOT SIGNED ON
 SHEETS.
  
 ** THE FOLLOWING WAS REDLINED ON PLANS AS ROOM
 DESIGNATIONS ARE NOW ON PLANS.
 THE SERVER ROOM AS SHOWN WILL NOT BE AN IT AND SHALL
 MEET CODE ACCORDINGLY. THIS SHALL BE VERIFIED IN FIELD.
 IF THIS IS AN IT ROOM, THEN PLEASE SEE REVISIONS PER
 NEC 645 AND NFPA-75 WILL BE REQUIRED.
 PLEASE SEE 2005 NEC/ NFPA-70 AND 2004 FBC W/ 2006
 REVISIONS WAS ALSO REDLINED ON PLANS AS THIS WAS
 MISSING. (MAY NOT STATE LATEST EDITION).
  
 ** COMMENT #1 ABOVE MUST BE ADDRESSED. ELECTRICAL PLANS
 ARE OK AND HAVE BEEN STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]