Plan Review Notes
Plan Review Notes For Permit 07060154
Permit Number 07060154
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-20 13:05:46*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH
 CORRELATE WITH THE PLANS. PLEASE SEE THE FIXTURES DO
 NOT MATCH. PLEASE SEE THE NUMBER AND TYPE OF FIXTURES
 DO NOT MATCH. PLEASE SEE THE WATTAGE OF FIXTURES ALSO
 DOES NOT MATCH.
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH
 PLANS AND CALCULATIONS.
 PLEASE SEE THE REQUIRED SIGNATURE FROM THE OWNER AGENT
 IS NOT ON THE SECOND SHEET AS REQUIRED.
 PLEASE SEE 13-415.1.AB.1.1.
  
 2) NOTE: PLEASE SEE THE RISER IS MISSING THE NEW
 FEEDERS TO THE NEW PANEL.
 240.4,310.16, FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE BOTH PANEL 100 AND 100A PANEL
 SCHEDULES ARE NOT SUBMITTED.
 PLEASE SEE THE CIRCUITING ON PLANS NEED TO COORDINATE
 WITH THE PANEL SCHEDULES TO BE SUBMITTED.
 PLEASE SEE 408.4, 310.16, 240.4. PLEASE SEE ALSO KNOW
 THE USE OF *GENERAL LIGHTING* OR GENERAL RECEPTACLES*
 IS NOT ACCEPTABLE ON PANEL SCHEDULE. EACH MUST BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. ALL
 ROOMS SHALL CONTAIN DESIGNATIONS. THE PANEL SCHEDULES
 NEED TO CORRELATE WITH THOSE DESIGNATIONS BY NUMERICAL
 OR NAMED DESIGNATIONS.
 PLEASE BE SURE THE PANEL INFORMATION IS STATED ON
 SCHEDULES: SIZE, VOLTAGE, AMPERAGE ETC.
  
 4) NOTE: PLEASE SEE THE PLANS DO NOT SHOW THE LOCATION
 OF THE NEW PANELS.
 PLEASE SEE 110.26, 408.7, 240.24.
  
 5) NOTE: PLEASE INDICATE NEW OR EXISTING GFI LOCATIONS
 FOR A/C EQUIPMENT.210.8, 210.63
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SUBMITTED
 FOR REVIEW AND/OR INFORMATION MISSING FROM PLANS, THERE
 MAY BE NEW COMMENTS ON THE NEXT REVIEW.
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved