| Date |
Text |
| 2007-06-20 13:05:46 | *** UNSAT 2ND REVIEW *** |
| | |
| | 1) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH |
| | CORRELATE WITH THE PLANS. PLEASE SEE THE FIXTURES DO |
| | NOT MATCH. PLEASE SEE THE NUMBER AND TYPE OF FIXTURES |
| | DO NOT MATCH. PLEASE SEE THE WATTAGE OF FIXTURES ALSO |
| | DOES NOT MATCH. |
| | PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH |
| | PLANS AND CALCULATIONS. |
| | PLEASE SEE THE REQUIRED SIGNATURE FROM THE OWNER AGENT |
| | IS NOT ON THE SECOND SHEET AS REQUIRED. |
| | PLEASE SEE 13-415.1.AB.1.1. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER IS MISSING THE NEW |
| | FEEDERS TO THE NEW PANEL. |
| | 240.4,310.16, FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE BOTH PANEL 100 AND 100A PANEL |
| | SCHEDULES ARE NOT SUBMITTED. |
| | PLEASE SEE THE CIRCUITING ON PLANS NEED TO COORDINATE |
| | WITH THE PANEL SCHEDULES TO BE SUBMITTED. |
| | PLEASE SEE 408.4, 310.16, 240.4. PLEASE SEE ALSO KNOW |
| | THE USE OF *GENERAL LIGHTING* OR GENERAL RECEPTACLES* |
| | IS NOT ACCEPTABLE ON PANEL SCHEDULE. EACH MUST BE |
| | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. ALL |
| | ROOMS SHALL CONTAIN DESIGNATIONS. THE PANEL SCHEDULES |
| | NEED TO CORRELATE WITH THOSE DESIGNATIONS BY NUMERICAL |
| | OR NAMED DESIGNATIONS. |
| | PLEASE BE SURE THE PANEL INFORMATION IS STATED ON |
| | SCHEDULES: SIZE, VOLTAGE, AMPERAGE ETC. |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS DO NOT SHOW THE LOCATION |
| | OF THE NEW PANELS. |
| | PLEASE SEE 110.26, 408.7, 240.24. |
| | |
| | 5) NOTE: PLEASE INDICATE NEW OR EXISTING GFI LOCATIONS |
| | FOR A/C EQUIPMENT.210.8, 210.63 |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SUBMITTED |
| | FOR REVIEW AND/OR INFORMATION MISSING FROM PLANS, THERE |
| | MAY BE NEW COMMENTS ON THE NEXT REVIEW. |
| | COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |