| 2007-06-21 18:58:30 | PLACED ON BOB BOARD ON 6/21 |
| 2007-06-21 18:48:57 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE 13-103, 13-415.1.1, .1.2 AS THE NEW |
| | SWITCHING DEVICES INSTALLED OR REPLACED MUST COMPLY |
| | WITH CHAPTER 13 OF THE FBC 2004 W/ 2006 REVISIONS. |
| | |
| | 2) NOTE: PLEASE SEE DEVICES ON PLANS WHICH ARE BEING |
| | SHOWN AS *E* FOR EXISTING YET THIS CAN NOT BE POSSIBLE |
| | WHEN THE DEMO AND ARCHITECTURAL PLANS DO NOT SHOW THESE |
| | WALLS YET? |
| | PLEASE COORDINATE THESE ITEMS. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE 408.4 AS THE CIRCUITING ON PANEL |
| | SCHEDULE NEEDS TO BE SPECIFIC TO ALL ROOMS AND AREAS IN |
| | WHICH THEY FEED. |
| | 4) NOTE: PLEASE CLARIFY CONDUCTOR SIZES ON NEW CIRCUITS |
| | ON PANEL. CAN BE TYPICAL IF ALL ARE THE SAME. 240.4, |
| | 310.16. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE CLARIFY NOT ON RISER FOR WHAT APPEARS |
| | TO BE A NEW PANEL ON SECONDARY SIDE OF THE TRANSFORMER. |
| | PLEASE SEE NOTES MENTIONS *MUST HAVE MCB WITH 100AMP |
| | OCP*. YET THE SENTENCE JUST FOLLOWING STATES *INSTALL |
| | IF REQUIRED*. IT IS UNCLEAR WHAT IS MEANT. |
| | PLEASE SEE THE CODE IS SPECIFIC IN 408.36 AND 240.21 |
| | THAT A MAIN OF SOME TYPE IS REQUIRED IN |
| | LIGHTING/APPLIANCE PANEL BOARDS AND ALSO MUST TERMINATE |
| | IN OCP BECAUSE OF TAPPED CONDUCTORS ON THE SECONDARY |
| | SIDE OF THE TRANSFORMER. |
| | ** PLEASE ADJUST NOTE. |
| | |
| | 6) NOTE: PLEASE CLARIFY CD LEVELS FOR ADA OF STROBES |
| | PER FBC 11-4.28.3(4). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |