| 2007-06-18 07:31:57 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE |
| | OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8). |
| | |
| | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD. ALSO SEE THE REFERENED CODES |
| | FOR THE 2004 FBC, CHANGE NOTES TO CORRECT CODE |
| | REFERENCE STANDARDS. SHEET A001. |
| | |
| | 3} PER 230.70(A)(1) A DISCONNECT IS REQUIRED OUTSIDE AT |
| | THE METER IF THERE IS MORE THAN 8 FEET OF UNPROTECTED |
| | CONDUCTORS ENTERING THE BUILDING(LOCAL AMENDMENT). |
| | |
| | 4} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 5} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 6} 240.24D) NOT IN VICINITY OF EASILY IGNITIBLE |
| | MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN |
| | THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN |
| | CLOTHES CLOSETS. SEE WATER HEATER. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |