Plan Review Notes
Plan Review Notes For Permit 07060142
Permit Number 07060142
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-18 07:31:57 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD. ALSO SEE THE REFERENED CODES
 FOR THE 2004 FBC, CHANGE NOTES TO CORRECT CODE
 REFERENCE STANDARDS. SHEET A001.
  
 3} PER 230.70(A)(1) A DISCONNECT IS REQUIRED OUTSIDE AT
 THE METER IF THERE IS MORE THAN 8 FEET OF UNPROTECTED
 CONDUCTORS ENTERING THE BUILDING(LOCAL AMENDMENT).
  
 4} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 6} 240.24D) NOT IN VICINITY OF EASILY IGNITIBLE
 MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN
 THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS. SEE WATER HEATER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  