2007-06-15 12:20:23 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 TWO COPIES OF ALL DOCUMENTS ARE REQUIRED PER 106.1 FBC
 AS AMENDED.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE COST
 OF LABOR AND MATERIAL FOR THE INSTALLATION OF ALL
 COMPONENTS UNDER THE SCOPE OF THIS PERMIT. FBC 108.3.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  