2007-08-20 08:15:02REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE GAS REVISION FOR PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. THE REVISED GAS ISOMERIC DOES NOT NOT INDICATE ALL
 THE CORRESPONDING LENGTHS OF THE INDICATED CUT SECTIONS
 OF PIPE. PLEASE CORRECT AND RESUBMIT.
  
 2. THE REVISED GAS ISOMETRIC DOES NOT INDICATE THE
 ABOVE GROUND PIPING MATERIAL. PLEASE CORRECT AND
 RESUBMIT.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: IN ORDER TO VERIFY THIS ALL THE CORRESPONDING
 LENGTHS OF THE CUT SECTIONS OF PIPE MUST BE INDICATED
 ON THE GAS REVISION.
  
 END OF COMMENTS:
  