| Notes |
| Date |
Text |
| 2007-08-10 17:31:07 | ** REDLINED PLANS. | | | | | | THE LIGHTING CONTROL DEVICE MUST BE A COMBINATION | | | DEVICE SUCH AS AN ULTRASONIC OCCUPANCY SENSOR AS A | | | MOTION DEVICE WILL NOT DETECT MOTION IN MULTIPLE STALLS | | | WITH PARTITIONS. | | | PLEASE SEE THIS IS MORE OF A LIFE SAFETY ISSUE. | | | PLEASE VERIFY AND ADJUST DEVICE IN FIELD. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | 561-805-6717 |
|