| 2007-06-10 12:20:06 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE MINOR MISPRINT FOR CODE ON |
| | FRONT SHEETS. SHOWS BOTH THE 2005 NFPA_70 AND THE 2002 |
| | NEC. |
| | |
| | 2) NOTE: PLEASE SEE SHEET A-3 WHICH MENTIONS NEW DEVICE |
| | FOR AUTO-SHUT OFF PER CHAPTER 13, HOWEVER PLEASE |
| | ELABORATE ON DEVICE FOR TYPE. IS THIS ULTRASONIC? IF |
| | ONLY MOTION, THEN WALL/STALL PARTITIONS WILL NOT |
| | PROVIDE NEEDED COVERAGE. |
| | PLEASE ALSO STATE MAXIMUM TIME FOR DEVICE. |
| | 13-415.1.ABC.1.1 |
| | |
| | 3) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP |
| | OF SOME TYPE FOR EACH RESTROOM PER LS 101 7.8, 7.9 |
| | WIRED TO LOCAL LIGHTING CIRCUIT PER 700.12F OF THE 2005 |
| | NEC> |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |