| Plan Review Notes For Permit 07060050 |
| Permit Number |
07060050 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-10 16:56:06 | ** REDLINED PLANS. | | | | | | THE LIGHTING CONTROL DEVICE MUST BE A COMBINATION | | | DEVICE SUCH AS AN ULTRASONIC OCCUPANCY SENSOR AS A | | | MOTION DEVICE WILL NOT DETECT MOTION IN MULTIPLE STALLS | | | WITH PARTITIONS. | | | PLEASE SEE THIS IS MORE OF A LIFE SAFETY ISSUE. | | | PLEASE VERIFY AND ADJUST DEVICE IN FIELD. |
|