| 2008-04-09 14:11:38 | REVISION DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVISION REVIEW: |
| | |
| | ******FROM PREVIOUS REVISION REVIEWS: |
| | |
| | A. SHT P1 OF 1 GAS REQUIRES A SEPARATE GAS PERMIT. |
| | SUBMIT THE FOLLOWING INFORMATION REQUIRED FOR GAS |
| | PERMIT: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.-(NEW) |
| | ****RESPONSE NOTED, BUT ITEM #30 BTU LOAD, (243MBH), |
| | DOES NOT REFLECT THE ISOMETRIC RISER DIAGRAM BTU LOAD |
| | INDICATED, (45MBH). |
| | ******RESPONSE NOTED, BUT NO MANUF. SHEETS WERE |
| | SUBMITTED THIS REVISION REVIEW. |
| | |
| | 6. N/A |
| | 7. N/A |
| | |
| | **********NEW COMMENT********* |
| | |
| | 1B. SHT P1 OF 1 AT THE TIME OF PERMIT ISSUE HAD |
| | REVISIONS 1 THRU 5, BUT THIS LATEST REVISION INDICATES |
| | REVISIONS 6 THRU 11 ON THE REVISION INDEX. SOME CHANGES |
| | ARE NOTED ON THE SANITARY RISER AND THE WATER RISER |
| | DIAGRAMS, BUT NO CLOUDS OR REVISION NUMBERS ARE |
| | INDICATED FOR REVISIONS 6 THRU 10. ALL REVISIONS SHALL |
| | BE CLOUDED AND NUMBERED TO TRACK ALL REVISIONS TO BE |
| | SUBMITTED. SECTION 106.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |