2008-03-19 18:05:35REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVISION REVIEW
  
 A. SHT P1 OF 1 GAS REQUIRES A SEPARATE GAS PERMIT.
 SUBMIT THE FOLLOWING INFORMATION REQUIRED FOR GAS
 PERMIT:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT THE PIPE SIZE FOR THE WATER HEATER IS
 REQUIRED TO BE 1-1/4", THE PIPE SIZE BETWEEN THE MOST
 UPSTREAM FRYER AND THE SECOND FRYER IS REQUIRED TO BE A
 MINIMUM 1-1/4", AND 1-1/4" IS REQUIRED FOR THE SUPPLY
 LINE & SHUT OFF VALVE TO ITEM 30, RESTAURANT RANGE AT
 243MBH. THIS IS PER TABLE 402.4(2) AT 150 FEET.
  
 3.BTU LOAD OFEACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE BTU LOAD INDICATED ON THE
 RISER FOR APPLIANCE #30, (RESTAURANT RANGE), DOES NOT
 REFLECT THE BTU LOAD INDICATED ON THE MANUF.
 SPECIFICATION SHEETS. MANUF. SHEETS INDICATE 6 BURNERS
 AT 33,000 BTU'S EACH PLUS 45,000 BTU'S FOR THE OVEN FOR
 A TOTAL OF 243,000 BTU'S. THE TOTAL BTU LOAD WILL
 CHANGE TO 942,000 FROM 744,000.
  
 4. OK
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.-(NEW)
 ****RESPONSE NOTED, BUT ITEM #30 BTU LOAD, (243MBH),
 DOES NOT REFLECT THE ISOMETRIC RISER DIAGRAM BTU LOAD
 INDICATED, (45MBH).
  
 6. N/A
 7. N/A
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  